Define total kvar and stage sizes against the load profile. Switching devices and the controller are confirmed for the selected panel.

EVA EUROPE / EQUIPMENT SOLUTIONS
Contactor-switched capacitor stages for suitable load conditions. Suitability must be checked against harmonics and operating duty; a conventional bank is not a universal solution for distorted networks.

TECHNICAL DETAILS
Define total kvar and stage sizes against the load profile. Switching devices and the controller are confirmed for the selected panel.
Check harmonic conditions and existing capacitors before selecting a conventional bank. A reinforced capacitor alone does not establish harmonic-filter performance.
Specify protection, discharge provisions, ventilation and service access. Do not assume all options in an old catalogue apply to the quoted configuration.
Values are retained from the existing product reference and are not universal limits for every supplier. Confirm the ratings and applicable configuration in the approved datasheet.
| Nominal Voltage | 400V AC |
| Frequency | 50 Hz |
| Response Time | 10sec-60sec |
| Switching Method | Compensation Contacts |
TECHNICAL SELECTION
System voltage, active / reactive power profiles, existing power factor and measured harmonics.
Required kvar, stage sizes, switching frequency, response time, measurement point and CT arrangement.
Existing panels and capacitors, ventilation, protection, available space and maintenance access.
Send a single-line diagram, technical specification or written requirements. Missing parameters are clarified before the final technical offer.
QUALITY & SUPPLY SCOPE
The agreed package may include datasheets, general arrangements, electrical diagrams, component schedules and installation / operating instructions. Required tests, verification records and applicable declarations are specified for the selected design.
The quotation identifies the equipment, accessories, interfaces, transport and included services. Installation, cable connections and commissioning are included only when expressly agreed.
COMMON QUESTIONS
They illustrate a product family or reference design. Manufacturer, ratings, dimensions, accessories and documents are identified in the agreed technical offer.
Send the equipment type and quantity, key parameters, project location and required date. Attach the available drawings or specification to your email.
ENQUIRE WITH EVA EUROPE
System voltage, active / reactive power profiles, existing power factor and measured harmonics.



eVAR-SC type conventional compensation panels are used where the harmonic pollution rate is above the limits and where the load changeover rate is slow. These panels are designed mainly to reduce system costs. These panels are manufactured with reactors as a standard, also, thyristors instead of contactors could be used. In addition, tube capacitors (cylindrical type) with 440V continuous operating voltage are used in these panels too.
eVAR brand thyristor module is used in eVAR-SC type compensation panels.
| Type | eVAR-SC |
| Nominal Voltage | 400V AC |
| Continuous Operating Voltage | 440V / 525V AC |
| Overcurrent | 2xIn |
| Frequency | 50 Hz |
| Ambient Temperature | -25°C – +55°C |
| Response Time | 10sec-60sec |
| Switching Method | Compensation Contacts |
| Protection Against Harmonics | Partially (reinforced type capacitor is used) |
| Metal-Sheet types and thicknesses | Stainless, electro galvanized (1,5mm – 2mm) |
| Standards | IEC-61439-1 and IEC-61439-2 |